Table 33:
Stator gain
UmaxEF [V]
Note
240
200
160
Default value
up to 120
8.8.3.2
Connecting and setting voltage inputs
The SIM module of REX060 has two analog output channels that shall be connected
to two voltage input channels of the IED.
If both stator and rotor protection are used, there are two possible methods to perform
the connection.
1. The recommended connection requires four analog channels of the IED: two IED
voltage channels are used for the measured quantities for STTIPHIZ; two more
IED voltage channels are used for the measured quantities for ROTIPHIZ.
REX060
X61
9
8
8
9
11
10
11
10
X81
STATOR MODULE SIM
ROTOR MODULE RIM
IED
VOLTAGE MEASURE (U)
VOLTAGE MEASURE (U)
CURRENT MEASURE (U)
CURRENT MEASURE (U)
IEC11000209-1-en.vsd
IEC11000209 V1 EN
Figure 163:
Separate analogue inputs for stator (STTIPHIZ) and rotor
(ROTIPHIZ) protection
2. It is possible to use a mixed connection that requires only two IED voltage
channels for both ROTIPHIZ and STTIPHIZ. REX060 outputs are connected in
series. This connection is not recommended and can be used only in applications
where it is proved the possibility to use it. The use of this connection leads to
reduced performances of both ROTIPHIZ and STTIPHIZ.
Section 8
1MRK 502 071-UEN -
Impedance protection
306
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...