15.10.2
Application
Single command, 16 signals (SINGLECMD) is a common function and always
included in the IED.
The IEDs may be provided with a function to receive commands either from a
substation automation system or from the local HMI. That receiving function block
has outputs that can be used, for example, to control high voltage apparatuses in
switchyards. For local control functions, the local HMI can also be used. Together
with the configuration logic circuits, the user can govern pulses or steady output
signals for control purposes within the IED or via binary outputs.
shows an application example of how the user can connect SINGLECMD
via configuration logic circuit to control a high-voltage apparatus. This type of
command control is normally carried out by sending a pulse to the binary outputs of
the IED. Figure
shows a close operation. An open breaker operation is performed
in a similar way but without the synchro-check condition.
Single
command
function
SINGLECMD
CMDOUTy
OUTy
Close CB1
&
User-
defined
conditions
Synchro-
check
Configuration logic circuits
en04000206.vsd
IEC04000206 V2 EN
Figure 298:
Application example showing a logic diagram for control of a circuit
breaker via configuration logic circuits
and figure
show other ways to control functions, which require steady
On/Off signals. Here, the output is used to control built-in functions or external
devices.
Section 15
1MRK 502 071-UEN -
Control
596
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...