mAHigh
: The mA value that corresponds to the highest tap position. Applicable when
reading of the tap position is made via a mA signal.
CodeType
: This setting gives the method of tap position reading.
UseParity
: Sets the parity check
On
/
Off
for tap position reading when this is made by
Binary, BCD, or Gray code.
tStable
: This is the time that needs to elapse after a new tap position has been reported
to TCMYLTC until it is accepted.
CLFactor
: This is the factor designated “a” in
operates at nominal load current (current measured on the HV-side), the ContactLife
counter decrements with 1, irrespective of the setting of
CLFactor
. The setting of this
factor gives the weighting of the deviation with respect to the load current.
InitCLCounter
: The ContactLife counter monitors the remaining number of
operations (decremental counter). The setting
InitCLCounter
then gives the start
value for the counter that is, the total number of operations at rated load that the tap
changer is designed for.
EnabTapCmd
: This setting enables/disables the lower and raise commands to the tap
changer. It shall be
On
for voltage control, and
Off
for tap position feedback to the
transformer differential protection T2WPDIF or T3WPDIF.
TCMYLTC and TCLYLTC Setting group
General
Operation
: Switching the TCMYLTC or TCLYLTC function
On
/
Off
.
IBase
: Base current in primary Ampere for the HV-side of the transformer.
tTCTimeout
: This setting gives the maximum time interval for a raise or lower
command to be completed.
tPulseDur
: Length of the command pulse (URAISE/ULOWER) to the tap changer. It
shall be noticed that this pulse has a fixed extension of 4 seconds that adds to the
setting value of
tPulseDur
.
15.5
Logic rotating switch for function selection and LHMI
presentation SLGAPC
15.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logic rotating switch for function
selection and LHMI presentation
SLGAPC
-
-
Section 15
1MRK 502 071-UEN -
Control
590
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...