To achieve a more correct regulation, an adjustment to a value of
j
2 slightly less than
-90° (2 – 4° less) can be made.
The effect of changing power factor of the load will be that
j
2 will no longer be close
to -90° resulting in U
L
being smaller or greater than U
B
if the ratio Rline/Xline is not
adjusted.
shows an example of this where the settings of
Rline
and
Xline
for
j
= 11°
has been applied with a different value of
j
(
j
= 30°).
U
B
jI
T
*
Xline
U
L
Xline
Rline
Zline
I
T
I
T
*
Rline
j=30
0
j
1
j
2
D
U
j
1
=11
0
-90
0
=-79
0
en06000630.vsd
IEC06000630 V1 EN
Figure 294:
Transformer with reverse reactance regulation poorly adjusted to the
power factor
As can be seen in figure
, the change of power factor has resulted in an increase of
j
2 which in turn causes the magnitude of U
L
to be greater than U
B
. It can also be noted
that an increase in the load current aggravates the situation, as does also an increase in
the setting of Zline (
Rline
and
Xline
).
Apparently the ratio Rline/Xline according to equation
, that is the value of
j
1
must be set with respect to the power factor, also meaning that the reverse reactance
method should not be applied to systems with varying power factor.
The setting of
Xline
gives the sensitivity of the parallel regulation. If
Xline
is set too
low, the transformers will not pull together and a run away tap situation will occur. On
the other hand, a high setting will keep the transformers strongly together with no, or
only a small difference in tap position, but the voltage regulation as such will be more
sensitive to a deviation from the anticipated power factor. A too high setting of
Xline
can cause a hunting situation as the transformers will then be prone to over react on
deviations from the target value.
There is no rule for the setting of
Xline
such that an optimal balance between control
response and susceptibility to changing power factor is achieved. One way of
determining the setting is by trial and error. This can be done by setting e.g.
Xline
equal
1MRK 502 071-UEN -
Section 15
Control
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
585
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...