magnitude of the source impedance and calculations must be made on a case by case
basis, as shown in figure
. Distance IEDs with separate impedance and directional
measurement offer additional setting and operational flexibility when it comes to
measurement of negative apparent impedance (as shown in figure
Negative IED impedance, negative fault current (current inversion)
is valid in Figure
and a fault occurs behind the capacitor, the
resultant reactance becomes negative and the fault current will have an opposite
direction compared with fault current in a power line without a capacitor (current
inversion). The negative direction of the fault current will persist until the spark gap
has flashed. Sometimes there will be no flashover at all, because the fault current is
less than the setting value of the spark gap. The negative fault current will cause a high
voltage on the network. The situation will be the same even if a MOV is used.
However, depending upon the setting of the MOV, the fault current will have a
resistive component.
X
X
X
C
S
>
+
11
EQUATION2036 V2 EN
(Equation 124)
The problems described here are accentuated with a three phase or phase-to-phase
fault, but the negative fault current can also exist for a single-phase fault. The
condition for a negative current in case of an earth fault can be written as follows:
1_ 1
0 _ 1
0 _
1_
3
2
2
×
> ×
+
+ ×
+
C
L
L
S
S
X
X
X
X
X
EQUATION1920 V1 EN
(Equation 125)
All designations relates to figure
. A good protection system must be able to cope
with both positive and negative direction of the fault current, if such conditions can
occur. A distance protection cannot operate for negative fault current. The directional
element gives the wrong direction. Therefore, if a problem with negative fault current
exists, distance protection is not a suitable solution. In practice, negative fault current
seldom occurs. In normal network configurations the gaps will flash in this case.
Double circuit, parallel operating series compensated lines
Two parallel power lines running in electrically close vicinity to each other and ending
at the same busbar at both ends (as shown in figure
) causes some challenges for
distance protection because of the mutual impedance in the zero sequence system. The
current reversal phenomenon also raises problems from the protection point of view,
particularly when the power lines are short and when permissive overreach schemes
are used.
en06000627.vsd
-jX
C
-jX
C
Z
AC
Z
CB
Z
AC
Z
CB
A
B
Z
m0AC
Z
m0CB
IEC06000627 V1 EN
Figure 126:
Double circuit, parallel operating line
1MRK 502 071-UEN -
Section 8
Impedance protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
245
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...