2
2
400
160
1000
=
=
=
UBase
ZBase
ohm
SBase
EQUATION1960 V1 EN
(Equation 151)
2
400
(
)
(
2) 2
20
2
52
5000
ZA Z line
Zsc station
j
j
j ohm
=
+
= +
+
= +
EQUATION1961 V1 EN
(Equation 152)
This corresponds to:
2
52
0.0125
0.325
0.325 88
160
j
ZA
j
pu
pu
+
=
=
+
=
Ð °
EQUATION1962 V1 EN
(Equation 153)
Set ZA to 0.32.
2
400
(
1)
32
5000
ZB
Zsc station
j
j ohm
=
=
=
EQUATION1963 V1 EN
(Equation 154)
This corresponds to:
32
0.20
0.20 90
160
j
ZB
j
pu
pu
=
=
=
Ð °
EQUATION1964 V1 EN
(Equation 155)
Set ZB to 0.2
This corresponds to:
2
20
0.0125
0.125
0.126 84
160
j
ZC
j
pu
pu
+
=
=
+
=
Ð °
EQUATION1966 V1 EN
(Equation 156)
Set ZC to 0.13 and
AnglePhi
to 88°
The warning angle (
StartAngle
) should be chosen not to cross into normal operating
area. The maximum line power is assumed to be 2000 MVA. This corresponds to
apparent impedance:
2
2
400
80
2000
U
Z
ohm
S
=
=
=
EQUATION1967 V1 EN
(Equation 157)
1MRK 502 071-UEN -
Section 8
Impedance protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
269
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...