Table 69:
General settings parameters for the Measurement function
Setting
Short description
Selected
value
Comment
Operation
Operation Off/On
On
Function must be
On
PowAmpFact
Amplitude factor to scale power
calculations
1.000
Typically no scaling is required
PowAngComp
Angle compensation for phase
shift between measured I & U
0.0
Typically no angle compensation
is required. As well here required
direction of P & Q measurement is
towards protected object (as per
IED internal default direction)
Mode
Selection of measured current
and voltage
Arone
Generator VTs are connected
between phases (V-connected)
k
Low pass filter coefficient for
power measurement, U and I
0.00
Typically no additional filtering is
required
UGenZeroDb
Zero point clamping in % of
Ubase
25%
Set minimum voltage level to 25%
IGenZeroDb
Zero point clamping in % of Ibase 3
Set minimum current level to 3%
UBase (set in
Global base)
Base setting for voltage level in
kV
15,65
Set generator rated phase-to-
phase voltage
IBase (set in
Global base)
Base setting for current level in A 3690
Set generator rated current
17.2
Gas medium supervision SSIMG
17.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Insulation gas monitoring function
SSIMG
-
63
17.2.2
Application
Gas medium supervision (SSIMG) is used for monitoring the circuit breaker
condition. Proper arc extinction by the compressed gas in the circuit breaker is very
important. When the pressure becomes too low compared to the required value, the
circuit breaker operation shall be blocked to minimize the risk of internal failure.
Binary information based on the gas pressure in the circuit breaker is used as an input
signal to the function. The function generates alarms based on the received
information.
17.2.3
Setting guidelines
The parameters for Gas medium supervision SSIMG can be set via local HMI or
Protection and Control Manager PCM600.
1MRK 502 071-UEN -
Section 17
Monitoring
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
635
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...