X1Rv
can be set to the same value as
X1Fw
•
K
equals side infeed factor at next busbar.
When the calculation of
X1Fw
gives a negative value the zone 1 must
be permanently blocked.
Fault resistance
The resistive reach is, for all affected applications, restricted by the set reactive reach
and the load impedance and same conditions apply as for a non-compensated network.
However, special notice has to be taken during settings calculations due to the ZnO
because 50% of capacitor reactance appears in series with resistance, which
corresponds to approximately 36% of capacitor reactance when the line current equals
two times the protective current level. This information has high importance for
setting of distance protection IED reach in resistive direction, for phase to earth- fault
measurement as well as, for phase-to-phase measurement.
Overreaching zone 2
In series compensated network where independent tripping zones will have reduced
reach due to the negative reactance in the capacitor and the sub-harmonic swinging the
tripping will to a high degree be achieved by the communication scheme.
With the reduced reach of the under-reaching zones not providing effective protection
for all faults along the length of the line, it becomes essential to provide over-reaching
schemes like permissive overreach transfer trip (POTT) or blocking scheme can be
used.
Thus it is of great importance that the zone 2 can detect faults on the whole line both
with the series capacitor in operation and when the capacitor is bridged (short
circuited). It is supposed also in this case that the reactive reach for phase-to-phase and
for phase-to-earth faults is the same. The X1Fw, for all lines affected by the series
capacitor, are set to:
•
X1
>= 1,5 · XLine
The safety factor of 1.5 appears due to speed requirements and possible under
reaching caused by the sub harmonic oscillations.
The increased reach related to the one used in non compensated system is
recommended for all protections in the vicinity of series capacitors to compensate for
delay in the operation caused by the sub harmonic swinging.
Settings of the resistive reaches are limited according to the minimum load
impedance.
1MRK 502 071-UEN -
Section 8
Impedance protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
253
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...