Settings on the local HMI under
Main menu/Configuration/Time/
Synchronization/TIMESYNCHGEN:1/General
:
•
fineSyncSource
can be set to something different to correlate events and data to
other IEDs in the station.
Two status monitoring signals can be:
•
SYNCH signal on the MUx function block indicates that protection functions are
blocked due to loss of internal time synchronization to the IED.
•
MUSYNCH signal on the MUx function block monitors the synchronization flag
smpSynch
in the datastream and IED hardware time synchronization.
SMPLLOST indicates that merging unit data are generated by internal substitution or
one/more channel's Quality is not good or merging unit is in Testmode/detailed
quality=Test, IED is not in test mode.
Using external clock for time synchronization
This example is not valid when GPS time is used for differential
protection, when PTP is enabled or when the PMU report is used.
IED
MU
data
PPS
IEC/UCA 61850-9-2LE
PPS / IRIG-B
STATION
CLOCK
IEC10000074=2=en=Original.vsd
IEC10000074 V2 EN
Figure 332:
Setting example with external synchronization
Settings on the local HMI under
Main menu/Configuration/Time/
Synchronization/TIMESYNCHGEN:1/IEC61850-9-2
:
1MRK 502 071-UEN -
Section 20
Station communication
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
695
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...