100
2
2
3
IBase
I
I
EQUATION1520 V5 EN
(Equation 262)
where:
I2
is the maximal negative sequence current during normal operating conditions, plus a margin of
10...20%
IBase
is the base current for the function according to the setting
GlobalBaseSel
14.2.3.4
Zero sequence based
The IED setting value
3U0>
is given in percentage of the base voltage
UBase
. The
setting of
3U0>
should not be set lower than the value that is calculated according to
.
100
3
0
3
0
3
UBase
U
U
EQUATION1521 V4 EN
(Equation 263)
where:
3U0
is the maximal zero sequence voltage during normal operation conditions, plus a margin of
10...20%
UBase is the base voltage for the function according to the setting
GlobalBaseSel
The setting of the current limit
3I0<
is done in percentage of
IBase
. The setting of
3I0<
must be higher than the normal unbalance current that might exist in the system.
The setting can be calculated according to equation
3 0
3 0
100
I
I
IBase
=
×
<
EQUATION2293 V3 EN
(Equation 264)
where:
3I0<
is the maximal zero sequence current during normal operating conditions, plus a margin of
10...20%
IBase
is the base current for the function according to the setting
GlobalBaseSel
14.2.3.5
Delta U and delta I
Set the operation mode selector
OpDUDI
to
On
if the delta function shall be in
operation.
1MRK 502 071-UEN -
Section 14
Secondary system supervision
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
475
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...