To ensure proper application of the IED for this power transformer it is necessary to
do the following:
1. Check that HV & LV CTs are connected to 5 A CT inputs in the IED.
2. For second solution make sure that LV delta connected CTs are DAB connected.
3. For star connected CTs make sure how they are 'star'red (that is, earthed) to/from
protected transformer.
4. Enter the following settings for all three CT input channels used for the HV side
CTs, see table
.
Table 18:
CT input channels used for the HV side CTs
Setting parameter
Selected value for both solutions
CTprim
400
CTsec
5
CTStarPoint
ToObject
5. Enter the following settings for all three CT input channels used for the LV side
CTs, see table
"CT input channels used for the LV side CTs"
.
CT input channels used for the LV side CTs
Setting parameter
Selected value for Solution 1 (star
connected CT)
Selected value for Solution 2
(delta connected CT)
CTprim
1500
1500
866
3
=
EQUATION1889 V1 EN
(Equation 18)
CTsec
5
5
CTStarPoint
ToObject
ToObject
To compensate for delta connected CTs, see equation
6. Enter the following values for the general settings of the differential protection
function, see table
.
Table 19:
General settings of the differential protection
Setting parameter
selected value for both Solution 1
(star conected CT)
Selected value for both Solution
2 (delta connected CT)
RatedVoltageW1
115 kV
115 kV
Rated VoltageW2
24.9 kV
24.9 kV
RatedCurrentW1
301 A
301 A
RatedCurrentW2
1391 A
1391 A
Table continues on next page
1MRK 502 071-UEN -
Section 7
Differential protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
143
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...