Simplified, the example can be shown as a triangle, see figure
ZA
ZB
Zload
R
X
en07000016.vsd
IEC07000016 V1 EN
Figure 139:
Simplified figure to derive StartAngle
0
0
32
52
arctan
arctan
arctan
+ arctan
= 21.8 + 33.0 55
80
80
³
=
»
ZB
ZA
angleStart
+
Zload
Zload
EQUATION1968 V2 EN
(Equation 158)
In case of minor damped oscillations at normal operation we do not want the
protection to start. Therefore we set the start angle with large margin.
Set
StartAngle
to 110°
For the
TripAngle
it is recommended to set this parameter to 90° to assure limited
stress for the circuit breaker.
In a power system it is desirable to split the system into predefined parts in case of pole
slip. The protection is therefore situated at lines where this predefined split shall take
place.
Normally the
N1Limit
is set to 1 so that the line will be tripped at the first pole slip.
If the line shall be tripped at all pole slip situations also the parameter
N2Limit
is set
to 1. In other cases a larger number is recommended.
Section 8
1MRK 502 071-UEN -
Impedance protection
270
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual