Operation
: This is used to disable/enable the operation of gas medium supervision i.e.
Off/On.
PresAlmLimit
: This is used to set the limit for a pressure alarm condition in the circuit
breaker.
PresLOLimit
: This is used to set the limit for a pressure lockout condition in the circuit
breaker.
TempAlarmLimit
: This is used to set the limit for a temperature alarm condition in the
circuit breaker.
TempLOLimit
: This is used to set the limit for a temperature lockout condition in the
circuit breaker.
tPressureAlarm
: This is used to set the time delay for a pressure alarm indication,
given in s.
tPressureLO
: This is used to set the time delay for a pressure lockout indication, given
in s.
tTempAlarm
: This is used to set the time delay for a temperature alarm indication,
given in s.
tTempLockOut
: This is used to set the time delay for a temperature lockout indication,
given in s.
tResetPressAlm
: This is used for the pressure alarm indication to reset after a set time
delay in s.
tResetPressLO
: This is used for the pressure lockout indication to reset after a set time
delay in s.
tResetTempLO
: This is used for the temperature lockout indication to reset after a set
time delay in s.
tResetTempAlm
: This is used for the temperature alarm indication to reset after a set
time delay in s.
17.3
Liquid medium supervision SSIML
17.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Insulation liquid monitoring function
SSIML
-
71
Section 17
1MRK 502 071-UEN -
Monitoring
636
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...