In case of a solid earth fault in high impedance earthed or unearthed systems the
primary value of Uo voltage will be equal to:
0
3
Ph
Ph
Ph
E
U
U
U
-
-
=
=
EQUATION1931 V2 EN
(Equation 11)
Figure
gives an overview of required actions by the user in order to make this
measurement available to the built-in protection and control functions within the IED.
L1
L2
L3
IED
6.6
3
100
kV
V
R
Uo
IEC06000603-4-en.vsdx
# Not Used
# Not Used
# Not Used
Protected Object
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AI N
1
2
3
4
5
IEC06000603 V4 EN
Figure 30:
Neutral point connected VT
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
91
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...