Setting
Values (Range)
Description
RevActPartBk(auto
matically reset)
Alarm
Auto Block
The risk of voltage instability increases as transmission
lines become more heavily loaded in an attempt to
maximize the efficient use of existing generation and
transmission facilities. In the same time lack of reactive
power may move the operation point of the power network
to the lower part of the P-V-curve (unstable part). Under
these conditions, when the voltage starts to drop, it might
happen that an URAISE command can give reversed result
that is, a lower busbar voltage. Tap changer operation
under voltage instability conditions makes it more difficult
for the power system to recover. Therefore, it might be
desirable to block TR1ATCC or TR8ATCC temporarily.
Requirements for this blocking are:
•
The load current must exceed the set value
RevActLim
•
After an URAISE command, the measured busbar
voltage shall have a lower value than its previous
value
•
The second requirement has to be fulfilled for two
consecutive URAISE commands
If all three requirements are fulfilled, TR1ATCC or
TR8ATCC automatic control will be blocked for raise
commands for a period of time given by the setting
parameter
tRevAct and the output signal REVACBLK will
be set. The reversed action feature can be turned off/on
with the setting parameter
OperationRA.
CmdErrBk
(manually reset)
Alarm
Auto Block
Auto&Man Block
Typical operating time for a tap changer mechanism is
around 3-8 seconds. Therefore, the function should wait for
a position change before a new command is issued. The
command error signal, CMDERRAL on the TCMYLTC or
TCLYLTC function block, will be set if the tap changer
position does not change one step in the correct direction
within the time given by the setting
tTCTimeout in
TCMYLTC or TCLYLTC function block. The tap changer
module TCMYLTC or TCLYLTC will then indicate the error
until a successful command has been carried out or it has
been reset by changing control mode of TR1ATCC or
TR8ATCC function to Manual and then back to Automatic.
The outputs CMDERRAL on TCMYLTC or TCLYLTC and
TOTBLK or AUTOBLK on TR1ATCC or TR8ATCC will be
activated depending on the actual parameter setting.
This error condition can be reset by the input RESETERR
on TCMYLTC function block, or alternatively by changing
control mode of TR1ATCC or TR8ATCC function to Manual
and then back to Automatic.
TapChgBk
(manually reset
Alarm
Auto Block
Auto&Man Block
If the input TCINPROG of TCMYLTC or TCLYLTC function
block is connected to the tap changer mechanism, then this
blocking condition will be active if the TCINPROG input has
not reset when the
tTCTimeout timer has timed out. The
output TCERRAL will be activated depending on the actual
parameter setting. In correct operation the TCINPROG
shall appear during the URAISE/ULOWER output pulse
and disappear before the
tTCTimeout time has elapsed.
This error condition can be reset by the input RESETERR
on TCMYLTC function block, or alternatively by changing
control mode of TR1ATCC or TR8ATCC function to Manual
and then back to Automatic.
Table continues on next page
Section 15
1MRK 502 071-UEN -
Control
572
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...