CT: 4000/5
VT: 13,5kV/110V
70MVA
13,2kV
3062A
65MVA
123/13kV
x
t
=10%
REG670
IEC10000102 V1 EN
Figure 78:
Application example for generator under-impedance function
The first under-impedance protection zone shall cover 100% of the step-up
transformer impedance with a time delay of 1.0s.
Calculate the step-up transformer impedance, in primary ohms, from the 13kV side as
follows: