9.14.3
Setting guidelines
9.14.3.1
Explanation of the setting parameters
Operation
: Set to
On
in order to activate the function; set to
Off
to switch off the
complete function.
StartCurr
: Operation phase current level given in % of
IBase
.
Characterist
: Selection of time characteristic: Definite time delay and different types
of inverse time characteristics are available; see Technical Manual for details.
tDef_OC
: Definite time delay. It is used if definite time characteristic is chosen; it
shall be set to
0 s
if the inverse time characteristic is chosen and no additional delay
shall be added. Note that the value set is the time between activation of the start and
the trip outputs.
k
: Time multiplier for inverse time delay.
tMin
: Minimum operation time for all inverse time characteristics. At high currents
the inverse time characteristic might give a very short operation time. By setting this
parameter the operation time of the step can never be shorter than the setting.
Operation_UV
: it sets
On
/
Off
the operation of the under-voltage stage.
StartVolt
: Operation phase-to-phase voltage level given in % of
UBase
for the under-
voltage stage. Typical setting may be, for example, in the range from 70% to 80% of
the rated voltage of the generator.
tDef_UV
: Definite time delay. Since it is related to a backup protection function, a
long time delay (for example
0.5
s or more) is typically used. Note that the value set
is the time between activation of the start and the trip outputs.
EnBlkLowV
: This parameter enables the internal block of the undervoltage stage for
low voltage condition; the voltage level is defined by the parameter
BlkLowVolt
.
BlkLowVolt
: Voltage level under which the internal blocking of the undervoltage
stage is activated; it is set in % of
UBase
. This setting must be lower than the setting
StartVolt
. The setting can be very low, for example, lower than 10%.
VDepMode
: Selection of the characteristic of the start level of the overcurrent stage as
a function of the phase-to-phase voltage; two options are available: Slope and Step.
See Technical Manual for details about the characteristics.
VDepFact
:
Slope mode
: it is the start level of the overcurrent stage given in % of
StartCurr
when the voltage is lower than 25% of
UBase
; so it defines the first point of
the characteristic (
VDepFact
*
StartCurr
/100*
IBase
; 0.25*
UBase
).
Step mode
: it is
the start level of the overcurrent stage given in % of
StartCurr
when the voltage is
lower than
UHighLimit
/100*
UBase
.
1MRK 502 071-UEN -
Section 9
Current protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
397
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...