Figure 211:
Supervision of fuses on generator circuit voltage transformers
10.5.3
Setting guidelines
The parameters for the voltage differential function are set via the local HMI or
PCM600.
The following settings are done for the voltage differential function.
Operation
:
Off
/
On
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
UBase
and
SBase
as applicable.
BlkDiffAtULow
: The setting is to block the function when the voltages in the phases
are low.
RFLx
: Is the setting of the voltage ratio compensation factor where possible
differences between the voltages is compensated for. The differences can be due to
different voltage transformer ratios, different voltage levels e.g. the voltage
measurement inside the capacitor bank can have a different voltage level but the
difference can also e.g. be used by voltage drop in the secondary circuits. The setting
is normally done at site by evaluating the differential voltage achieved as a service
value for each phase. The factor is defined as U2 ·
RFLx
and shall be equal to the U1
voltage. Each phase has its own ratio factor.
1MRK 502 071-UEN -
Section 10
Voltage protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
427
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...