UHighLimit
: when the measured phase-to-phase voltage is higher than
UHighLimit
/
100*
UBase
, than the start level of the overcurrent stage is
StartCurr
/100*
IBase
. In
particular, in
Slope
mode it define the second point of the characteristic (
StartCurr
/
100*
IBase
;
UHighLimit
/100*
UBase
).
9.14.3.2
Voltage-restrained overcurrent protection for generator and step-up
transformer
An example of how to use VRPVOC function to provide voltage restrained
overcurrent protection for a generator is given below. Let us assume that the time
coordination study gives the following required settings:
•
Inverse Time Over Current IDMT curve: IEC very inverse, with multiplier k=1
•
Start current of 185% of generator rated current at rated generator voltage
•
Start current 25% of the original start current value for generator voltages below
25% of rated voltage
To ensure proper operation of the function:
1. Set
Operation
to
On
2. Set
GlobalBaseSel
to the right value in order to select the Global Base Values
Group with
UBase
and
IBase
equal to the rated phase-to-phase voltage and the
rated phase current of the generator.
3. Connect three-phase generator currents and voltages to VRPVOC in the
application configuration.
4. Select
Characterist
to match the type of overcurrent curves used in the network
IEC Very inv.
5. Set the multiplier
k
=
1
(default value).
6. Set
tDef_OC
=
0.00
s, in order to add no additional delay to the trip time defined
by the inverse time characteristic.
7. If required, set the minimum operating time for this curve by using the parameter
tMin
(default value 0.05 s).
8. Set
StartCurr
to the value 185%.
9. Set
VDepMode
to
Slope
(default value).
10. Set
VDepFact
to the value 25% (default value).
11. Set
UHighLimit
to the value 100% (default value).
All other settings can be left at the default values.
9.14.3.3
General settings
Operation
: With the parameter
Operation
the function can be set
On
/
Off
.
Common base IED values for primary current (
IBase
), primary voltage (
UBase
) and
primary power (
SBase
) are set in Global base values for settings function GBASVAL.
Setting
GlobalBaseSel
is used to select a GBASVAL function for reference of base
values.
Section 9
1MRK 502 071-UEN -
Current protection
398
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...