20.4.2
MULTICMDRCV and MULTICMDSND
20.4.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Multiple command and receive
MULTICMDRCV
-
-
Multiple command and send
MULTICMDSND
-
-
20.4.2.2
Application
The IED provides two function blocks enabling several IEDs to send and receive
signals via the interbay bus. The sending function block, MULTICMDSND, takes 16
binary inputs. LON enables these to be transmitted to the equivalent receiving
function block, MULTICMDRCV, which has 16 binary outputs.
20.4.2.3
Setting guidelines
Settings
The parameters for the multiple command function are set via PCM600.
The
Mode
setting sets the outputs to either a
Steady
or
Pulsed
mode.
20.5
SPA communication protocol
20.5.1
Application
SPA communication protocol is an alternative to IEC 60870-5-103, and they use the
same rear communication port.
When communicating with a PC connected to the utility substation LAN via WAN
and the utility office LAN (see Figure
), and when using the rear optical Ethernet
port, the only hardware required for a station monitoring system is:
•
Optical fibres from the IED to the utility substation LAN
•
PC connected to the utility office LAN
Section 20
1MRK 502 071-UEN -
Station communication
700
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...