Figure 160:
Effective high-resistance generator earthing via a distribution
transformer
Another alternative is shown in figure
(High-resistance earthing via a grounded
wye-broken delta transformer). In this case the transformer must withstand the large
secondary current caused by primary earth fault. The resistor typically has to be
divided as shown in figure
to limit the voltage to the injection equipment in case of
earth fault at the generator terminal. This voltage is often in the range 400 – 500 V. As
the open delta connection gives three times the zero sequence phase voltage this gives
too high voltage at the injection point if the resistance is not divided as shown in the
figure
. By dividing the resistor in two parts it shall be ensured that maximum
voltage imposed back on injection equipment is equal to or less than 240V.
Section 8
1MRK 502 071-UEN -
Impedance protection
302
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual