0,03-0,1-0,3-0,5-1-3
   
       by d

irect setting

5-10-30 

by

 SETUP

INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1
      by d

irect setting

3-5-10 

by

 SETUP

Not available
(see version 
ELR-3As)

3 E D 3 0 x

 

Code

Power supply

230 V c.a. 

110 V c.a.

G

E

ELR-3A

  Electronic Earth-leakage Protection Relay

For instance ELR-3A 

110 V a.c..

.

supplied by 

3ED30E

RGU - 10 C

24/ 48 V c.a/a.c

24/120 V c.c/d.c 

T

GENERAL DESCRIPTION

45

52,5

43,5

85

67,9

 DIN 46277 (EN 50022)

Weight :168 gr

Fixed by rail

 Rated current: 6 Ac.a
 Rated voltage : 230 Vc.a 

1-2       External Input Trip/ Reclose                                                              Optocoupled

   

3       Not used  

                                                   

   

4       Pre-alarm output relay common

                                                     

   

5       Pre-alarm output relay, NC   

                                                 

   

6       Pre-alarm output relay, NA   

                                                 

   

7       Not used 

                                                    

   

8       Input Current sensor 1S2

                                                      

   

9       Input Current sensor 1S1        

 

   

10       Supply 230 Va.c (Phase or Neutral)  

   

11       Supply 230 Va.c (Neutral or Phase)

  

   

12       Not used 

   

   

13       Tripping output relay NO

                                                      

   

14       Tripping output relay NC       

                                                      

   

15       Tripping output relay COMMON

                                                      

Rated current: 6Ac.a. 
Rated voltage: 230 Va.c    

TERMINAL DESCRIPTION                                           FEATURES 

- Device with 2 independent, programmable relays, one main relay one prealarm.
- It has 2 outputs. Main trip relay and prealarm signal relay.
- It has 1 potential free input for external ON/OFF.
- Mounting in DIN rail 46277 

(EN 50022)

 or PANEL 72x72 by means accesories

 

(3EDA03)

- Associated to a 

CT-1/... 

Series external, toroidal current transformer.

- It verifies connection with external transformer 

CT-1/... 

by inductive

 

tests.

- Leakage detection and measurement is via calculating its true effective value (TRMS)

.

- Displays setting values and instant current different to its associated units

PRELIMINARY CONSIDERATIONS  

CHECKS ON RECEPTION 

On receving the instrument, check the following points:
            - The unit’s specifications are the same as those on your order.
            - Check that the device has not suffered any damage during transport.

You can download more information from CONTREL website, www.contrel.it 

SAFETY PRECAUTIONS 

The  staff  using  or  handling  the  unit  must  follow  the  common  safety  measures  and 
warnings included in the instruction manual.

The ELR-3A unit has been specifically designed for its installation in a electric board, 
enclosure to a DIN rail or mounted in panel by means of accessories. It has a flashing 
green led (ON) when it is operation and, therefore, it shows that there is voltage and 
current  in  the  electronic  circuit.  The  user  must  make  sure  that  the  equipment  is  not 
connected to the power supply at all the times, even when the LED is not flashing.

Likewise,  the  power  supply  circuit  must  have  a  built-in  circuit  breaker  or  equivalent 
device to disconnect the unit from the power.supply network.

INSTALLATION AND START-UP   

The user must take into account and observe the informations and warnings included in 
this instruction manual to guarantee the correct operation of the equipment and comply 
whit the safety specifications. The equipment must not turned on until is fully installed in 
the electrical panel.

¡IMPORTANTE!

IMPORTANT!

The  unit´s  protections  systems  might  not  be  effective  if  the  unit  is  used  for 
purpose other than those specifications by the manufacturer.

Disconnect  the  equipment  from  the  power  supply  when  the  unit´ssafety  protection 
systems are not working or there are signs of a problem (in case of visible damage). In this 
case, contact a qualified technical service or with our own technical service .

DIN rail installation. Through the CBT must pass all live conductors supplyng electrical 
energy to loads or part of the installation which requires it to earth leakage protection with 
this device. In single-phase installation (phase and neutral, L and N), three phase - 3 
wires (three phases, L1, L2 and L3) or three phases - 4 wires (L1, L2, L3 and N). All 
connections should be inside the electrical board. Please note that with the connected 
equipment,  terminals  and  opening  covers  or  removing  elements,  can  give  access  to 
dangerous  parts  to  touch.  The  equipment  must  not  be  used  until  it  has  completely 
finished installation. The unit must be connected to a power supply circuit protected by 
fuses in line with the range and power consumption. In turn, the supply circuit must be 
provided with a circuit breaker or equivalent device to disconnect the equipment from the 

2

mains. During the wiring cable is advisable a section permitted between 1 - 1.5 mm . A 
recommended torque of 0.5-0.6 N.m. Cable Stripping Tools length 7 mm.        
                                              

contrel

contrel

ELR-3A

TECHNICAL FEATURES

- Tipo Relay type: Electronic class A. High frequency current filtering.
- Reclosing type: Manual via RESET button or by cutting power supply. 
- Rated power supply voltage:    230 (± 20%) 50/60 Hz, 6 VA
 

 

               110 (± 20%) 50/60Hz, 6 VA

 

 

               24-48 V a.c. / 24-120 V d.c., 6 VA, ± 20%, 4 W

- Operating temperature:            10...+50ºC
- Relative humidity:                      5%...95% RH (Non-condensing)
- Maximum operating altitude:     2000m
- IP Protection:
Assembled equipment (front): IP 41
Non assembled equipment (sides and rear cove): IP 20

- Connections:
Permissible cable section:                  0,127-2,8082 mm
Recommended tightening torque        0.5-0.6 Nm
Length of cable to strip:                       7mm
Recommended screwdrivers:             Bar 0.4 x 2.5 x 80 mm, length 160mm

Switch Output contact features:                                             13-14-15 and 4-5-6                           
Rated current/Maximum instant current:                                 6/10 A a.c.
Rated voltage/Maximum switching voltage:                            230/275 V a.c.
Rated load in AC1:                                                                  2500 V·A    
Contacts protected by varistor (max. Operating voltage):       275 Va.c. 
Rated load in Ac1:  

 

 

 

    1-2 

Input Opto-coupled
Maximum voltage:  

 

 

 

    230 V a.c.+20%; 0,7 W

- Safety:    

 

 

 

    CAT III (EN61010)

STANDARD

Meet with standard IEC62020 and IEC60947-2 Annex- M.             .  