Contrel ELR-3A Series Instruction Manual Download Page 2

AUTO

                 

SENSIVITY SETTING

CONTACTS POLARITIES

SETTING RESET PREALARM 

            0,03-0,1-0,3-0,5-1-3-5-10-30 A
      

 
   

ROTATIONAL BUTTON SETUP

DELAY SETTING

0,02-0,1-0,2-0,3-0,4-0,75-1-3-5-10 s

 INS-SEL

Id

YELLOW LED: Prealarm

 

BUTTON RESET

BUTTON TEST

                                                I

D

N

TRIPPING CURRENT TRESHOLD

            td

DELAY TIME

INSTANT LEAKAGE CURRENT VALUE

 

SETUP SETTINGS

- Communications (RGU-10C)
- Frecuency 50/60 Hz
- Range values current / time delay.
 
PREALARM SETTINGS
- Current adjustment (%I

D

N).

- Delay time

DESCRIPTION LEDS AND BUTTONS 

 

- Shows equipment status via a display and 2 LED's.
- 5 button equipment setup and setting.
- 2 button equipment TEST and RESET

LED AND DISPLAY INDICATION  

- MAIN TRIP RELAY 

LED and display signals a

 

change of status by changing from green to red.

 

Display event type messages or values

PREALARM SIGNAL. 

The yellow LED only 

comes  on  when  current  leakage  exceeds  the 
preset prealarm threshold

                     

Cause of trip                       Message display

T

est                                           TESt

Remote signal  ON/OFF            EXIT
Current leakage                         TRIP 

                            Otros MENSAJES por display        Mensaje  display

                         Others  messages by display              

SAVE      Enters setting values 

                                              

EXIT          Exits setting mode                  
OVR          Current leakage reading off scale  
Errt            Error of current sensor connection                         

RECLOSING THE EQUIPMENT   

BY 

TRIP

.  A  manual 

RESET

,  or  disconnection  supply  is  required  to  return  to  the

 

equipment´s

 

initial status.

- BY 

PREALARM

.A manual 

RESET 

has to be performed if it is in non-automatic mode to 

cancel

 

this status

MAIN RELAY PARAMETER SETTING 

t  

I

 

and std/+ )

d

d

   

MAIN RELAY PARAMETER SETTING 

t  

I  

and std/+ )

d

d

   

- SETTING TRIP DELAY 

t

d.

 

The message and two values appear on the screen after 

pressing the button. The lowest value indicates the current set value and the
highest is the values to be configured which are displayed by pressing     .The selected 
value to be saved is displayed by showing the message SAVE

-  SENSITIVITY  SETTING 

I

d.

The  same  operation  as  above  setting  is  carried  out  by

 

pressing

 

I

d.

- SAFETY SETTING std/+ 

The required safety type through changing the trip contact

 

polarity is selected by pressing this button. (Std) Standard nothing appears on the

 

display 

and (+) Positive, the      symbol appears

+

+

A short press on 

PROG 

enters the prealarm channel activating the 

Alarm 

message on

 

the display.

- DELAY SETTING, 

t

d

 

. Select the time delay for giving the prealarm signal.

SENSITIVITY SETTING 

I

d

 

.

 

Select the equipment's prealarm threshold. Selected

sensitivity stated as % in the main channel(OFF-50-60-70-80-MAIN).

- POLARITY SETTING, std/+

. Select the prealarm output signal polarity.

-  SETTING  OF  RESET  OF  PREALARM,  A

uto

Activating        ,  the  equipment 

automatically resets the prealarm when the leakage current drops below the preset alarm 
threshold

REC

ELR-3A

  Electronic Earth-leakage Protection Relay

contrel

SETUP SETTINGS 

A long press on 

PROG 

activates the setting menu . Using the 

PROG 

and     buttons

in this operating mode moves and changes the preset equipment values in the differen
setting submenus. 

Pushbutton PROG

FREC

50 Hz

60 Hz

10 s, 30 A 

1 s, 3 A Hz

LIM

Button

With the button the submenus are browsed 
and  with  the  button  the  values  to  be 
selected  are  displayed  to  enter  the  value. 
The  equipment  configures  the  value  by 
displaying “

SAVE

” on the display and then 

exits  Setting  Mode  If  the  keypad  remains 
inactive  for  a  certain  time,  the  equipment 
automatically  exits  Setting  Mode  and 
displays  “EXITS”  without  changing  the 
setting. 
.

Electrical useful life for AC loads

o. of cycles. (See graph

: N

)

 Maximun DC Load Breaking Capacity:  Maximum opening current. (See graph

)

OUTPUT RELAY FEATURES 

GREEN LED: Equipment ON

Pag. 2/3