TR1ATCC then compares this voltage with the set voltage,
USet
and decides which
action should be taken. To avoid unnecessary switching around the setpoint, a
deadband (degree of insensitivity) is introduced. The deadband is symmetrical around
USet
, see figure
, and it is arranged in such a way that there is an outer and an inner
deadband. Measured voltages outside the outer deadband start the timer to initiate tap
commands, whilst the sequence resets when the measured voltage is once again back
inside the inner deadband. One half of the outer deadband is denoted ΔU. The setting
of ΔU, setting
Udeadband
should be set to a value near to the power transformer’s tap
changer voltage step (typically 75–125% of the tap changer step).
Voltage Magnitude
Umax
U
2
Uset
U
1
Umin
Ublock
0
Raise Cmd
*) Action in accordance with setting
Security Range
Lower Cmd
IEC06000489_2_en.vsd
D
D
U
U
D
U
in
D
U
in
*)
*)
*)
IEC06000489 V2 EN
Figure 282:
Control actions on a voltage scale
During normal operating conditions the busbar voltage U
B
, stays within the outer
deadband (interval between U1 and U2 in figure
). In that case no actions will be
taken by TR1ATCC. However, if U
B
becomes smaller than U1, or greater than U2, an
appropriate raise or lower timer will start. The timer will run as long as the measured
voltage stays outside the inner deadband. If this condition persists longer than the
preset time delay, TR1ATCC will initiate that the appropriate ULOWER or URAISE
command will be sent from TCMYLTC or TCLYLTC function block to the
transformer tap changer. If necessary, the procedure will be repeated until the
magnitude of the busbar voltage again falls within the inner deadband. One half of the
inner deadband is denoted ΔU
in
. The inner deadband ΔU
in
, setting
UDeadbandInner
should be set to a value smaller than ΔU. It is recommended to set the inner deadband
to 25-70% of the ΔU value.
This way of working is used by TR1ATCC while the busbar voltage is within the
security range defined by settings
Umin
and
Umax
.
A situation where U
B
falls outside this range will be regarded as an abnormal situation.
When U
B
falls below setting
Ublock
, or alternatively, falls below setting
Umin
but still
above
Ublock
, or rises above
Umax
, actions will be taken in accordance with settings
for blocking conditions (refer to table
If the busbar voltage rises above
Umax
, TR1ATCC can initiate one or more fast step
down commands (ULOWER commands) in order to bring the voltage back into the
security range (settings
Umin
, and
Umax
). The fast step down function operation can
be set in one of the following three ways: off /auto/auto and manual, according to the
Section 15
1MRK 502 071-UEN -
Control
552
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...