Table 15:
CT input channels used for the LV side CTs
Setting parameter
Selected value for both solutions
CTprim
800
CTsec
5
CTStarPoint
ToObject
5. Enter the following settings for all three CT input channels used for the HV side
CTs, see table
.
Table 16:
CT input channels used for the HV side CTs
Setting parameter
Selected value for solution 1 (star
connected CT)
Selected value for solution 2
(delta connected CT)
CTprim
300
300
173
3
=
EQUATION1888 V1 EN
(Equation 17)
CTsec
5
5
CTStarPoint
From Object
ToObject
To compensate for delta connected CTs, see equation
6. Enter the following values for the general settings of the Transformer differential
protection function, see table
Table 17:
General settings of the differential protection function
Setting parameter
Select value for solution 1 (star
connected CT)
Selected value for solution 2
(delta connected CT)
GlobalBaseSelW1
CTPrim / GlobalBaseSelW1
(CTPrim /
GlobalBaseSelW1) / sqrt(3)
GlobalBaseSelW2
CTPrim / GlobalBaseSelW2
(CTPrim /
GlobalBaseSelW2) / sqrt(3)
GlobalBaseSelW3
CTPrim / GlobalBaseSelW3
(CTPrim /
GlobalBaseSelW3) / sqrt(3)
ConnectTypeW1
STAR (Y)
STAR (Y)
ConnectTypeW2
delta=d
star=y
1)
ClockNumberW2
1 [30 deg lag]
0 [0 deg]
1)
ZSCurrSubtrW1
On
Off
2)
ZSCurrSubtrW2
Off
Off
TconfigForW1
No
No
TconfigForW2
No
No
Table continues on next page
1MRK 502 071-UEN -
Section 7
Differential protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
141
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...