background image

(Date / Name): 20.04.2011 Fu/Su  

Drawing no.: 12280-0701-05 

Page 1 of 28 

Name: TR 800 WEB 

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected] 

 

 

Operating Instructions   

 

Universal-Relay TR 800 Web

  

 
 
 
 
 

 

 

 

 

 
 
 
 
 
 

   

 

 

 

 
 
 
Software version 1.1.9 
 

 

MINIPAN

®

 digital panel meters, temperature- and mains controlling, 

special purpose instruments for customer requirements    

www.ziehl.com

 

 

Summary of Contents for TR 800 Web

Page 1: ...tronik GmbH Co KG Daimlerstr 13 D 74523 Schwäbisch Hall Tel 49 791 504 0 Fax 56 email info ziehl de Operating Instructions Universal Relay TR 800 Web Software version 1 1 9 MINIPAN digital panel meters temperature and mains controlling special purpose instruments for customer requirements www ziehl com ...

Page 2: ...n the unit 9 8 8 Connection to network and controls 9 8 9 Find the unit in the network 10 8 9 1 DHCP server 10 8 9 2 Default IP Adress 10 10 10 10 10 8 9 3 Bonjour 11 8 9 4 UPnP 11 8 9 5 Information about the login window 11 8 10 Make the basic network settings 12 8 11 Sensor settings 13 8 12 Configuring the alarms 14 8 13 Alarm email 15 8 14 System 16 8 15 User management access control 17 8 16 L...

Page 3: ... signals from up to 8 inputs Up to 8 limits one per input can be programmed for each of the 4 output relays 2 Overview of functions 8 measuring inputs o Pt 100 Pt 1000 in 2 or 3 wire connection o KTY 83 or KTY 84 o Thermocouples type B E J K L N R S T o DC 0 10 V DC 0 4 20 mA o Resistance 500 Ohm resistance 30 kOhm 4 relay outputs each potential free change over contact Ethernet interface http htt...

Page 4: ... active 6 LEDs yellow sensors Illuminated Displays the sensor value belonging to the LED in the digital display Flashes Sensor error in the corresponding sensor circuit 7 LEDs yellow relay state Illuminated The relay belonging to the LED is picked up Off The relay belonging to the LED is released 8 Digital display 4 digits Display of sensor value Display of error codes Display of menu and configur...

Page 5: ...representative Instead of the industrial norms and regulations written in this instructions manual valid for Europe you must observe out of their geographical scope the valid and relevant regulations of the corresponding country DANGER Hazardous voltage Will cause death or serious injury Turn off and lock out all power supplying this device before working on this device Observe the maximum tempera...

Page 6: ...he measured values and evaluates them Configuration and operation are performed with a computer through a web browser A setting can be made for each sensor o Assignment limit Alarm as desired o Alarm active inactive o Limit for alarm on o Limit for alarm off For Relays K1 K4 Alarm 1 Alarm 4 can be set individually o Response delay and switch back delay o Relay on off during alarm operating or clos...

Page 7: ...OFF Relay is released LED red Alarm 1 4 Flashes 1 4 Response delay is active Flashes 4 1 switch back delay is active Flashes 1 1 Ready for switch back reset with press SET RESET button 2s or close ext Reset Y1 Y2 On Alarm on OFF Alarm off LED yellow Sensor 1 8 ON Measurement of selected sensors in the display Flashes Error in sensor circuit LED red Sensor error On Fault in a sensor circuit Defecti...

Page 8: ... nc8 not connected 8 1008 type Pt 100 810008 type Pt 1000 8 838 KTY 83 8 848 KTY 84 8th 8 thermocouples 80 108 voltage input 0 10 V 80 208 current input 0 20 mA 84 208 current input 4 20 mA 8r5008 resistance 500 Ohm 8r30 08 resistance 30 K Ohm 8diff8 difference 8IP 8 IP address 8IP 8 IP address 8 1928 1 digit of IP address 8π1688 2 digit of IP address 8 1 3 digit of IP address 8_ 958 4 digit of IP...

Page 9: ... X 8 10 Make the basic network settings X 8 11 Sensor settings X 8 13 Configure the alarms X 8 13 Alarm email X 8 14 System X 8 15 User management access control X 8 16 Logging X 8 17 View measurements and alarms sensor simulation 8 7 Switching on the unit Apply supply voltage to terminals A1 and A2 Ca 2s long all LEDs and the digital display illuminate 8 8 8 8 The TR 800 Web is now ready to opera...

Page 10: ...ch to IP 10 10 10 10 sketch Point 8 8 Requires a reboot of webserver press RESET button in the digital display boot flashes start duration ca 1 min User management is deactivated http Port 80 und https Port 443 Note The following actions can only be performed with administrator rights Enter this command into your PC in the input prompt command line route add 10 10 10 10 xxx xxx xxx xxx xxx xxx xxx...

Page 11: ...ng from Win XP Note not available if the http port has been switched off Start network browser network environment Symbols for show Network UPnP devices must be active Double click on the device found The TR 800 Web homepage opens in the web browser Close the login window with the OK button without user name and without password 8 9 5 Information about the login window Closing the login window cli...

Page 12: ...k parameters here Ask your network administrator if necessary Note Switch off http with http Port 0 UDP settings The device provides a facility to download data via the UDP protocol The related UDP port can be changed here RS485 interface If the device is operated on a RS485 interface the parameters and the protocol can be selected here Email settings The TR 800 Web provides a facility for sending...

Page 13: ... choose a total wire resistance for 2 wires 2 wire technique wire resistance compensation To compensate the wire resistance short circuit the wires nearby the sensor and measure the wire resistance We recommend to use 2 or better 3 wires for each sensor With 2 wire connection and a common wire for all signals all sensor measuring currents will be added on the common wire Thus the value of the comp...

Page 14: ...arm Relay on alarm on The relay picks up during an alarm off The relay releases during an alarm Alarm on error on This alarm is non delayed triggered during device error sensor error even if the sensors are not active off This alarm is not triggered during a sensor error device error If a sensor triggers an alarm and this sensor has an error then the alarm is non delayed reset even if Alarm locked...

Page 15: ...f Measurement value Alarm on Alarm off if Measurement value Alarm off 8 13 Alarm email In addition to an alarm message on Relay K1 K4 an email can also automatically be sent Box Description Dropdown list Selects for which alarm 1 4 an email will be sent Email Alarm ON Email will be sent if an alarm occurs Email Alarm OFF Email will be sent if an alarm expires Recipient Enter email addresses separa...

Page 16: ...R 800 system time Function Description Save device settings Every change in the device can be taken over with the Save button a new configuration point is automatically added It is saved with the date time and the user A comment can be added to these points Save device settings on a PC Activate the desired configuration Click the link Download config file The file is downloaded to the PC Copy devi...

Page 17: ...ww ziehl com website as needed 8 15 User management access control The TR 800 Web has user management with access control Stipulate the administrator user and guest access here as required If the user management is switched on checkbox active a password can be assigned to each user and administrator To do that click on the Change password button In the window that opens enter the first and second ...

Page 18: ... alarm changes are logged in two ring memories 100 ring memories are stored internally Recording time depending on the setting of the interval current ring memory recording time 100 ring memory backups Interval 1500 data records days days month year 00 00 02 0 50 00 0 0 17 4 0 6 0 0 00 00 10 4 10 00 0 2 17 4 0 6 0 0 00 00 30 12 30 00 0 5 52 1 1 7 0 1 00 01 00 25 00 00 1 0 104 2 3 4 0 3 00 03 00 75...

Page 19: ...ith the extension upl uploaded and then renamed to csv The filename uses the local time format Inside the files the selected time format is used see System Settings In the case of transmission problems see the Transmission Log file Upload Selection present data and alarms The file current csv will be uploaded Current data memory The file values csv will be uploaded The content consists of 1500 rec...

Page 20: ...anonymous login username User name for login on the FTP server Password Password for the login on the FTP server delete before rename This is to activate when the FTP server rename a file into an existing file is not accepted This is in some Windows FTP servers server program needed See Transmission Log 8 17 View measurements and alarms sensor simulation Here all measurements can be clearly viewed...

Page 21: ...layed or hidden The colour and the format of the line and the marker can be set Checkbox details 100 logged points see Point 8 16 are displayed in the chart Using the older newer recent buttons one can navigate chronologically in both directions Complete checkbox The entire logged area 1500 points is shown in the chart Absolute checkbox Unit of the y axis corresponds to the sensor metrics Relative...

Page 22: ... are available o active day no time control alarm day values always apply o active night no time control alarm night values always apply o active scheduled the specified switchover times apply The times for the night values are entered into the table Up to four switch times can be set for each day of the week To activate these times the active check box for the corresponding day needs to be set Ex...

Page 23: ...ine help of TR 800 Web or can be downloaded via the Internet www ziehl com 9 4 FTP Upload Option Recorded measurements and alarm states can be time controlled saved to an FTP server as a CSV file Furthermore it is possible to continuously transmit the current values or time controlled or event controlled change in an alarm state 9 5 AJAX data interface The AJAX data interface makes data measuremen...

Page 24: ...nected the wrong way around Remedy Check the thermocouple and connect it correctly if applicable Er 8 appears in the digital display Cause Internal device error Remedy Switch unit off and back on If the error message continues to appear the unit must be returned to the factory for repair LED Rx and Tx constantly flash Cause The unit is momentarily performing a software update Remedy A software upd...

Page 25: ...itching capacity max 1250 VA ohmic load max 120 W at DC 24 V UL electrical ratings E214025 250 V ac 5 A resisitive 240 V ac 1 2 hp 120 V ac 1 4 hp B 300 pilot duty UL 508 Nominal operational current Ie AC15 Ie 3 A Ue 250 V DC13 Ie 2 A Ue 24 V Ie 0 2 A Ue 125 V Ie 0 1 A Ue 250 V Recommended fuses for contact T 3 15 A gL Expected contact life mechanical 3 x 107 operations Expected contact life elect...

Page 26: ...RS 485 interface Baud rate 4800 9600 19200 Baud Parity N O E none odd even Wire length 1000 m at 19200 Baud ZIEHL RS485 protocol Time end request start answer 5 50 ms Send data without request 3 s 3 s 200 ms Send data without request 170 ms 170 ms 50 ms Sensor connection Measuring cycle time depending on sensor type Sensor 1 3 5 7 0 340 3 s Sensor 2 4 6 8 0 340 3 s Pt 100 Pt 1000 according to EN 6...

Page 27: ...on from Full Scale 0 10 V 12 kΩ 27 V 0 1 a voltage 20 V will affect other channels 0 4 20 mA 18 Ω 100 mA 0 5 Temperature drift 0 02 K Measuring time 40 ms Measuring of resistance Precision 0 0 500 0 Ω 0 2 of measured value 0 5 Ω Precision 0 30 00 kΩ 0 5 of measured value 2 Ω Sensor current 0 6 mA Measuring time 220 ms Housing Design V8 switchgear mounting Dimensions W x H x D 140 x 90 x 58 mm Moun...

Page 28: ...ing 4 Plombenlasche latch for sealing 5 Frontplatteneinsatz front panel 6 Kennzeichen für unten position downward 7 Riegel bei Wandbefestigung mit Schrauben Riegelbohrung Ø 4 2 mm for fixing to wall with screws Ø 4 2 mm Sie finden diese und weitere Betriebsanleitungen soweit verfügbar auch in Englisch auf unserer Homepage www ziehl de You find this and other operating manuals on our homepage www z...

Reviews: