(Date / Name): 20.04.2011 Fu/Su
Drawing no.: 12280-0701-05
Page 11 of 28
Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
8.9.3 Bonjour
Plugin for Internet Explorer (www.apple.com/bonjour)
Plugin for Firefox Browser (www.bonjourfoxy.net)
Optional in the Safari browser (switch on)
Note: not available if the http-service has been disabled.
Windows: Download the plugin for Internet Explorer from the Internet and install it
Mac OS X: Bonjour is integrated in the system (Safari browser)
Linux:
Bonjour not available
Start browser and let TR 800 Web search with Bonjour.
Double click on the device found
The TR 800 Web homepage opens in the web browser
Close the login window with the OK button (without user name and without
password)
8.9.4 UPnP
Available for Windows starting from Win XP
Note: not available if the http port has been switched off
Start network browser (network environment),
("Symbols for show Network UPnP devices" must be active)
Double click on the device found
The TR 800 Web homepage opens in the web browser
Close the login window with the OK button (without user name and without
password)
8.9.5 Information about the login window
Closing the login window (click on OK button) is delayed a couple of seconds as data still
needs to be transmitted in the background.
If the user admin/access control is inactive (default) the login window is not visible.
The user management/access control is always deactivated if the slide switch is set to
IP=10.10.10.10 (see Points 8.8 and 8.9.2).
If the user admin/access control is active (see Point 8.15), the Username and Password
must be entered.
Entry is case-sensitive.
Guest access (if activated, see Point 8.15) is made by logging in without any user name and
password. Guests can only view the "Measurements" and "Sensors" web pages. It is not
possible to change the parameters.