(Date / Name): 20.04.2011 Fu/Su
Drawing no.: 12280-0701-05
Page 25 of 28
Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
Login window cannot be closed
Remedy
Close the browser window and then reopen it
Data graphics, Logging, it appears a later time stamp
Remedy
Check the date and time in the menu
“System".
Erase all data logs with button "erase log" in menu “Logging”
13. Technical Data
Rated supply voltage Us
AC/DC 24
– 240 V
Tolerance
Power consumption
DC 20,4 - 297 V
< 4 W
AC 20 - 264 V 50-60 Hz
<13 VA
Relay output
4 x 1 changeover (CO)
Switching voltage
max. AC 415 V
Switching current
max. 5 A
Switching capacity
max. 1250 VA (ohmic load)
max.120 W at DC 24 V
UL electrical ratings:
E214025
250 V ac, 5 A, resisitive
240 V ac, 1/2 hp
120 V ac, 1/4 hp
B 300
– pilot duty, UL 508
Nominal operational current Ie
AC15
Ie = 3 A
Ue = 250 V
DC13
Ie = 2 A
Ue = 24 V
Ie = 0,2 A Ue = 125 V
Ie = 0,1 A Ue = 250 V
Recommended fuses for contact
T 3,15 A (gL)
Expected contact life mechanical
3 x 10
7
operations
Expected contact life electrical
1 x 10
5
operations at AC 250 V / 6 A
Test conditions
EN 61010-1
Rated impulse voltage
4000 V
Overvoltage category
Contamination level
III
2
Rated insulation voltage Ui
300 V
On-time
100%
Environmental conditions
Ambient temperature range
Storage temperature range
Altitude
Climatic conditions
External wiring temperature range
-20 °C ... +65 °C
-
20 °C … +70 °C
Up to 2000 m
5
– 85 % rel. humidity, no condensation
-
5 °C … +70 °C
Vibration resistance EN 60068-2-6
2…25 Hz ±1,6 mm
25 ... 150 Hz 5 g