8.12 Configuring the alarms
Box
Description
Day / Night
Switch the display of the alarm values for day / night operation.
Definition of the switchover times in the "Time control" menu
Attention: Only affects the values of "Alarm ON" and "Alarm OFF"
Alarm name
State a name for the respective alarm
Delay
on: Time (in s) during which an alarm is suppressed:
off: Backshift (in s) after an alarm
Relay on alarm
on: The relay picks up during an alarm
off: The relay releases during an alarm
Alarm on error
on: This alarm is non-delayed triggered during:
device error
sensor error (even if the sensors are not "active")
off: This alarm is not triggered during a sensor error / device error.
If a sensor triggers an alarm, and this sensor has an error, then
the alarm is non-delayed reset (even if "Alarm locked '= on).
Alarm locked
on: An alarm occurring one time will not be automatically reset. Only
pressing reset (close "SET/RESET" button ≥ 2s or ext. Y1/Y2 reset or
break of supply voltage Us) resets the alarm.
off: Alarm not locked
Sensor no.
active:
Switches the alarm for this sensor on/off
Alarm on : Value at which the device triggers an alarm
Alarm off: Value at which the device resets an alarm