8.9 Find the unit in the network
Prerequisite: Web browser Internet Explorer 7,8 or Firefox 3 (tested).
The TR 800 Web provides four facilities to find itself in the network:
8.9.1 DHCP server
In the network, there is a DHCP server; newly added units automatically are assigned an
IP address
Query of the IP address in the unit
Press the DOWN button 2x, then the SET button
IP address appears in the digital display
Status of DHCP query is displayed (
off
/
on
/
FAIL
)
Start web browser and enter the IP address in the address line [Return]
The TR 800 Web homepage opens in the web browser
Close the login window with the OK button (without user name and without password)
If the network logon fails via DHCP, a network configuration will be performed based on
zeroconf (IP = 169.254.x.x).
8.9.2 Default IP- Address 10.10.10.10
! Use this setting for configuration only.
Push slide switch to IP 10.10.10.10 (sketch Point 8.8)
Requires a reboot of webserver (press RESET button), in the digital display
boot
flashes (start duration ca. 1 min)
User management is deactivated, http-Port = 80 und https-Port = 443
Note: The following actions can only be performed with administrator rights.
Enter this command into your PC in the input prompt (command line):
route add 10.10.10.10 xxx.xxx.xxx.xxx
(xxx.xxx.xxx.xxx= IP address of PC)
Route for the TR 800 Web
ping 10.10.10.10
Connection test
TR 800 Web replies
Reply from 10.10.10.10: Bytes=32 Time=3ms TTL=32
Reply from 10.10.10.10: Bytes=32 Time=1ms TTL=32
Ping statistic for 10.10.10.10:
Package: Sent = 4, Received = 4, Lost = 0 (0% loss),
Connection okay
Start web browser and enter the IP address (10.10.10.10) in the address line [Return]
The TR 800 Web homepage opens in the web browser
Close the login window with the OK button (without user name and without password)
Make the basic network settings
Push the slide switch to IP USER (sketch Point 8.8)
Requires a reboot of webserver (press RESET button), in the digital display
boot
flashes (start duration ca. 1-2 minutes
Note: The settings made in the web browser under "Network" are only effective after the
slide switch is switched to IP User and the unit has been rebooted (press RESET button).