8.11 Sensor settings
Select "Sensors" in the web browser menu
Make the settings for the connected sensor types here. A name can be assigned for each
sensor for clear identification.
Box
Description
Sensor name
State a name for sensors 1 - 8
Current value
Display the measurement with the unit
Sensor type
Select the sensor type
Wire
Compensation
only with Pt100 / Pt1000: Select "3-wire" or choose a total wire
resistance for 2-wires.
2-wire technique wire resistance compensation:
To compensate the wire resistance short-circuit the wires nearby the
sensor and measure the wire resistance. We recommend to use 2 or
better 3 wires for each sensor.
With 2-wire connection and a common wire for all signals, all sensor
measuring currents will be added on the common wire. Thus the value
of the compensation wire resistance RK must be calculated as follows:
RK = (n+1) x RL/2
(RL = wire resistance of two wires, n = number of sensors)
Scaling on
Zero-point
Full-scale
Dec. point
Scaling for temperature sensors not available.
Zero-point scaling
Full-scale scaling
Decimal point scaling
Unit
°C, °F, V, mA, Ω, kΩ, % and a freely-definable unit (box can be edited).
°C and °F are available for temperature sensors.