(Date / Name): 20.04.2011 Fu/Su
Drawing no.: 12280-0701-05
Page 27 of 28
Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
Thermocouples according to EN 60 584, DIN 43 710:
Measuring range °C
Precision
Type
min
Max
B
0
1820
±2 °C
T > 300°C
E
-270
1000
±1 °C
J
-210
1200
±1 °C
K
-200
1372
±2 °C
L
-200
900
±1 °C
N
-270
1300
±2 °C
R
-50
1770
±2 °C
S
-50
1770
±2 °C
T
-270
400
±1 °C
Temperature drift
< 0,01 % / K
Measuring error of the sensor wire
+0,25
µV / Ω
Reference junction
±5 °C
Measuring time
<= 440 ms
Voltage- / Current input
Input
resistance
Maximum
Input signal
Precision
(from Full-Scale)
0
– 10 V
12 kΩ
27 V
0,1 %
a voltage > 20 V will affect
other channels
0/4-20 mA
18 Ω
100 mA
0,5 %
Temperature drift
< 0,02 %/K
Measuring time
<= 40 ms
Measuring of resistance:
Precision
0,0 … 500,0 Ω
0,2 % of measured value
± 0,5 Ω
Precision
0…30,00 kΩ
0,5 % of measured value
± 2 Ω
Sensor-current
≤0,6 mA
Measuring time
<= 220 ms
Housing
Design V8, switchgear mounting
Dimensions (W x H x D)
140 x 90 x 58 mm
Mounting height
55 mm
Wire connection, one wire
each 1 x 1,5 mm
2
Stranded wire with insulated ferrules each 1 x 1,0 mm
2
Torque of screw
0,5 Nm (3,6 lb.in)
Protection class housing
IP 30
Protection class terminal
IP 20
Fitting position
any
Installation
Snap mounting on mounting rail 35 mm according to
EN 60 715 or with screws M 4
(2 additional bars, not included
in delivery)
Weight
app. 370 g
Subject to technical changes