RELION® PROTECTION AND CONTROL

615 series

IEC 60870-5-103 Communication

Protocol Manual

Summary of Contents for Relion 615 series

Page 1: ...RELION PROTECTION AND CONTROL 615 series IEC 60870 5 103 Communication Protocol Manual...

Page 2: ......

Page 3: ...Document ID 1MRS759001 Issued 2019 04 30 Revision A Product version 5 0 FP1 Copyright 2019 ABB All rights reserved...

Page 4: ...bed in this document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of the ABB G...

Page 5: ...ted and communicate data and information via a network interface which should be connected to a secure network It is the sole responsibility of the person or entity responsible for network administrat...

Page 6: ...al equipment for use within specified voltage limits Low voltage directive 2014 35 EU This conformity is the result of tests conducted by the third party testing laboratory Intertek in accordance with...

Page 7: ...ic counters 11 IEC 60870 5 103 process data 12 IEC 60870 5 103 data objects 12 Indications 12 ASDU 2 type fault number and relative time data 13 Configuring of IEC 60870 5 103 indications 13 Class 1 e...

Page 8: ...ction type 25 Device identification code 25 Time synchronization 26 Block monitoring 26 Disturbance recorder file transfer 26 Disturbance recorder file directory ASDU 23 26 Disturbance recorder channe...

Page 9: ...s the communication system engineer or system integrator responsible for pre engineering and engineering the communication setup in a substation from a protection relay s perspective The system engine...

Page 10: ...61850 engineering guide Point list manual Cyber security deployment guideline GUID 12DC16B2 2DC1 48DF 8734 0C8B7116124C V2 EN Figure 1 The intended use of documents during the product life cycle Prod...

Page 11: ...nder certain operational conditions operation of damaged equipment may result in degraded process performance leading to personal injury or death Therefore comply fully with all warning and caution no...

Page 12: ...ssages and monitored data names are shown in Courier font When the function starts the START output is set to TRUE This document assumes that the parameter setting visibility is Advanced Section 1 1MR...

Page 13: ...pplication data 5 4 Definition and coding of application information elements 5 5 Basic application functions 5 6 Conformance testing guidelines 5 103 Companion standard for the informative interface...

Page 14: ...roblems with older installations every available IEC 60870 5 103 process data point can be freely remapped with PCM600 All the mapped data is not in use by default 2 2 Documentation Address informatio...

Page 15: ...overflows should be treated and reported ASDU type 2 data is generally supported This means the generation of a fault number and a relative time stamp for protection related Class 1 events Despite the...

Page 16: ...o protocol instances is in use I3CLPRT EC_FRZ STATUS GUID B230DC02 9257 4A70 A16D 2FC4A9D35CD6 V1 EN Figure 2 Function block By default Instance 1 is active in the IED but needs to be set On by the Op...

Page 17: ...frames and link errors The serial drivers COMn have their own diagnostic counters for lower level serial communication character error and link messages The COMn counters count all the messages on th...

Page 18: ...ntical For a list of the available data objects see the point list manual 3 3 2 Indications The IEC 60870 5 103 standard defines indications to be of ON OFF type The value coding for indications is al...

Page 19: ...tions Change GI assignment of indications Change ASDU type used by the indications Change the data coding value DPI representation four pole objects only Suppress falling edge Class 1 events non stand...

Page 20: ...erflow operation in the IED The setting parameters are located in Configuration Communication IEC 60870 5 103 I3C0n parameter suffix n 1 or 2 depending on the instance Class1OvInd n takes the overflow...

Page 21: ...0870 5 103 Class 1 data In older IED versions the LED object had only two positions Off and Alarm red The corresponding IEC 60870 5 103 Class1 LED data area shows DPI values off 01 for Off and values...

Page 22: ...red maximum current and voltage values during a fault and fault locator registrations For example also tap changer position values can be obtained through TypeID 4 There is no internal prioritization...

Page 23: ...be controlled ON If the IED is in local mode the remote CB controls are rejected 3 3 4 1 Circuit breaker control model Circuit breaker can only be controlled with DIRECT ON OFF commands This is due to...

Page 24: ...and is rejected on link level Link NAK DFC 1 Remote command performed on a non existing object The command is rejected on link level Link NAK DFC 0 In the last two cases the DFC flag is used to distin...

Page 25: ...the corresponding values are set as constant 0 Trailing 0 values are cut from the frame and the frame becomes shorter The default function type information number definitions for frame 6 are FUN 10 IN...

Page 26: ...IEC 60870 5 103 measurand Values 1 2 and 2 4 are standard values but the IED can actually accept any value For example scale 4 0 for IL1 enlarges the measurand range to 4 0 In 4 0 In The IEC 60870 5...

Page 27: ...to collect registrations belonging to the same fault situation ASDU 4 events can easily fill up the Class 1 event buffer The fault record can for example be configured to register only after an operat...

Page 28: ...esent IED real time Thereafter ASDU205 counter events are created into Class1 buffer Some alternatives for EC_FRZ activation A common alternative for the operation is that counters should be frozen an...

Page 29: ...ll over value The roll over values can be defined through the Communication Management tool Scale value Default setting is 1000000000 999999999 1 3 3 7 Accessing of non protocol mapped data The protec...

Page 30: ...y protocol as regular protocol application data General purpose input object and OR function block may cause delays to time stamps 3 4 Other IEC 60870 5 103 data 3 4 1 Changing of parameter setting gr...

Page 31: ...all IEC 60870 5 103 data points that have their function type defined as 0 The user has to assure that no similar IEC 60870 5 103 point definitions already exist with the same function type and inform...

Page 32: ...ts into IEC 60870 5 103 disturbance data Disturbance files are also available as standard COMTRADE files through PCM600 or WHMI IEC 60870 5 103 disturbance recorder spontaneous Class 1 notification me...

Page 33: ...stem Disturbance recorder files can be deleted by the IEC 60870 5 103 master The recorder file is deleted by the IED after it has been sent to the IEC 60870 5 103 master according to the standard Dist...

Page 34: ...channel signals are available or not The IED may measure voltages either between phase and ground or between phases The contents in ACC 5 8 and 69 71 are coupled directly to these voltage measurement...

Page 35: ...nless the IEC 60870 5 103 master does not abort the transmission Disturbance recorder transfer verification The IEC 60870 5 103 disturbance recorder file transfer implemented in the IED has been verif...

Page 36: ...cycle operates as defined by the standard GI optimization strives to send less data to the master through the Class 1 report The GI optimization in the IED is based on two facts It is enough to send a...

Page 37: ...at has been done in advance This configuration can be modified with PCM600 It is also possible to start a completely new configuration from an emptied configuration state in Application Configuration...

Page 38: ...32...

Page 39: ...led Serial port 1 COM 1 2 COM 2 1 COM 1 COM port Address 1 255 1 1 Unit address Mapping select 1 2 1 1 Mapping selection Start delay 0 20 char 1 4 Start frame delay in chars End delay 0 20 char 1 4 En...

Page 40: ...use 0 User frame 1 Standard frame 1 2 Standard frame 2 3 Standard frame 3 4 Standard frame 4 5 Standard frame 5 6 Private frame 6 7 Private frame 7 1 Not in use Active Class2 Frame 3 Frame4InUse 1 No...

Page 41: ...f Monitoring Direction Internal Overflow 0 False 1 True 0 False Internal Overflow TRUE System level overflow occured indication only EC_FRZ 0 False 1 True 0 False Control point for freezing energy cou...

Page 42: ...36...

Page 43: ...flow control DPI Double point information EIA 485 Serial communication standard according to Electronics Industries Association EMC Electromagnetic compatibility FAN Fault number FUN Function type GI...

Page 44: ...ger Reset CU Reset communication unit Reset FCB Reset flow control bit SOF Status of fault SW Software TEST Disturbance data recorded in test mode bit TM Disturbance data transmission in progress bit...

Page 45: ...39...

Page 46: ......

Page 47: ......