340 Verification and validation
Validation of the SS1 function
1. Make sure that the input for the SS1 function is configured according to the wiring
diagram.
2. Make sure that the SS1 function, and SAR1 setting or time monitoring limit is
configured correctly according to your design. For a configuration example, see
chapter
How to configure SS1 with time monitoring (SS1-t)
on page
, or
to configure SS1 with ramp monitoring (SS1-r)
. Check these
settings:
Activation:
•
•
.
•
Note:
activation can also come from the PROFIsafe
Acknowledgement:
•
•
if manual acknowledgement is
used.
Functionality:
•
= Version 1
•
SS1-r ramp zero speed delay for STO
(if used)
•
•
•
drive parameter
23.23 emergency stop time
, if
= 0 ms
•
if with safe speed estimation:
•
a) If ramp monitoring is in use:
-
= SS1-r
-
-
-
OR
b) If time monitoring is in use:
-
= SS1-t
-
.
Indication:
•
•
•