Safety functions 123
D
Zero speed limit (parameter
): Speed limit to define the motor as stopped.
The safety function is completed and the SSE completed indication (parameter
goes on. The acknowledgment becomes allowed.
SLS trip limit (A)
Step Description
1
The SLS request is received, the motor speed is below the SLS limit positive (B) and
the FSO starts the SLS monitoring. The SLS indication (parameter
,
,
) goes on.
2
The motor speed goes above the SLS limit positive (B).
3
The motor speed reaches the SLS trip limit positive (A). The SLS indication goes off.
4
After time C has elapsed, the FSO activates the SSE function and the drive starts the
ramp down the motor speed. SAR0 parameter
5
The motor speed goes below the SLS limit positive (B) and the SLS indication goes on.
6
The motor speed goes below the zero speed limit (D). The motor has stopped and the
FSO opens the drive STO circuit. The SSE completed indication goes on.
7
The SLS request is removed. The SLS monitoring is still on (acknowledgement method
is manual or from a safety PLC).
8
The SLS function is acknowledged and the FSO stops the SLS monitoring. The SSE
function is acknowledged with the same acknowledgement. The indications go off.
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...