46 Safety functions
General
Safety function request
A safety function can be activated locally from FSO digital inputs, from a safety PLC,
in FSO internal fault situations or by another safety function (see section
Dependencies between safety functions
on page
If you want to control a safety function with a push button, connect an activation
button to an FSO digital input. 24 V in the input is the non-request for a safety
function and 0 V is the request.
Note:
The FSO module executes the requested safety function even if the request is
removed before the function has reached the acknowledgement criteria.
Note:
With one input it is possible to activate up to two separate safety functions.
A request activates both functions simultaneously. For the execution order, see
section
Priorities between safety functions
(page
).
Note:
The FSO module does not react to activation requests of the safety functions
during the boot.
Acknowledgement methods
You can configure the acknowledgement method separately for the start-up, STO
(SSE and SS1 always end in drive STO), SLS and POUS safety functions.
ID
Description
A
Normal request: The request is recognized when the button is pressed. The pressing
time of the button must be at least 20 ms.
Note
: The safety function request must be removed before the acknowledgement is
accepted.
B
Short low signals (less than 20 ms) are ignored.
C
Safety function is activated when the request signal last at least 20 ms.
A
Button release allowed
20 ms
B
Time
Button pressed
C
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...