Verification and validation 349
Validation of the cascaded safety function
Without a PROFIsafe communication bus, you can cascade only safety functions
which have a primary and a secondary digital input: STO, SS1, SSE, SLS1. Repeat
the cascading validation procedure to all cascaded safety functions in your
application.
This example shows how to validate the SSE function in a cascaded system
(Cascade A) as shown in section
.
1. Make sure that the cascaded safety function(s) are configured according to the
wiring diagram.
2. Make sure that the cascaded safety functions are configured correctly according
to your design. For a configuration example see chapter
. Check these settings:
Master FSO:
•
•
•
= automatic
•
•
•
•
Follower FSO modules (check the settings in each follower FSO module in the
cascade chain):
•
•
= Automatic
•
•
3. Activate cascaded safety function from the master FSO module.
4. Check that the correct safety function is activated in the whole cascaded chain.
5. Check that all cascaded safety functions are operating correctly according to the
design in each of the cascaded FSO module.
6. Deactivate cascaded safety functions from the master FSO, and acknowledge the
safety function by using manual acknowledgement if in use.
7. Check that the follower FSO modules are acknowledged.
Repeat this procedure for the Cascade B chain if in use.
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...