PROFIsafe 197
6. To check the Device number of the FENA module, select the
General
tab.
Diagnostic messages related to F-Parameters
The diagnostics messages in this table are caused by problems in the
F-Parameter processing that takes place only when the controller station sends the
F-Parameters to FENA. This happens normally only when the controller station starts
up the PROFINET communication with the FENA module.
Value
(hex)
Description
Notes
64
(0x0040)
Mismatch of safety destination
address (F_Dest_Add).
F_Dest_Add did not match the value
configured in the safety parameters
(
65
(0x0041)
Safety destination address is not valid
(F_Dest_Add).
F_Dest_Add of 0 or FFFFh is not allowed.
A valid F_Dest_Add is within range
1...65534.
66
(0x0042)
Safety source address is not valid
(F_Source_Add).
F_Source_Add of 0 or FFFFh is not
allowed.
A valid F_Source_Add is within range
1...65534.
67
(0x0043)
Safety watchdog time value is 0 ms
(F_WD_Time).
Watchdog time 0 ms is not allowed.
A valid F_WD_Time is within range
1...65535.
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...