378 Technical data
Basic safety data
The FSO-12 module is a type B safety component as defined in IEC 61508-2.
The FSO-12 data related to safety standards IEC 61508, EN/IEC 61800-5-2,
EN ISO 13849-1 and EN/IEC 62061 is listed below for the different subsystems
within the FSO module.
Maximum useful mission time (
T
m
) for the FSO module module is 20 years. After 20
years, the module has to be replaced.
The given safety data applies with proof test interval T1 = 20 years (high demand and
continuous mode of operation) and T1 = 2 years or T1 = 5 years (low demand mode
of operation). Make sure that the proof test is performed within this time (see also
section
EN 61508
EN ISO 13849-1
EN/IEC 62061
SIL
up to 3
PL
up to e
SILCL
3
SC
3
3AXD10000006135.xlsm L
PROFI-
safe
1)
1-ch. DI,
pulses
2-ch. DI,
pulses
1-ch. DI,
no pulses
2-ch. DI,
no pulses
Logic 1,
1-ch. DI or
DO, no
pulses
2)
Logic 2,
other
cases
2)
SIL/SILCL
3
3
3
2
3
1
3
PL
e
d
e
c
e
c
e
PFH (1/h)
1.0E-09
5.1E-10 1.8E-12 9.0E-09 2.3E-12 4.5E-09 4.4E-11
PFD
avg
(T1 = 2 a)
8.8E-06 4.8E-06 2.4E-08 7.9E-05 2.8E-08
5.2E-05 4.1E-07
PFD
avg
(T1 = 5 a)
2.2E-05 1.2-E5
4.8E-08 2.0E-04 5.8E-08 1.3E-04
9.9E-07
MTTF
D
(a)
114155
17844
12648
12648
12648
5048
5048
HFT
N/A
0
1
0
1
0
1
Cat.
4
2
3
1
3
1
3
SFF (%)
99.00
99.64
99.94
94.02
99.92
86.82
93.48
DC (%)
99.00
91.99
99.00
0.00
98.74
80.26
90.23
3AXD10000006135.xlsm L
1)
We assume conservatively that PFH =
λ
d = 1, FIT = 1e-9 1/h,
MTTF
D
= 1/
λ
d = 1/(1e-9 1/h) = 1e9 h = 114155 a. Based on the BGIA Report 2/2008e:
Functional Safety of Machine Controls – Application of EN ISO 13849, ch. 6.2.17.
2)
Either logic subsystem (Logic 1 or Logic 2) is included in each safety function implemented
with the FSO. If the safety function contains any 1-channel digital input or output of the FSO
with non-pulsed signals, the subsystem "Logic 1” must be used. Otherwise the subsystem
"Logic 2" is used.
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...