![ABB FSO-12 User Manual Download Page 79](http://html.mh-extra.com/html/abb/fso-12/fso-12_user-manual_2726079.webp)
Safety functions 79
Step Description
1
The SSE request is received (for example, from the I/O). The FSO activates the drive
STO function and starts a counter for time A.
2
After time A has elapsed, the FSO activates the SBC and starts a counter for time B.
3
After time B has elapsed, the FSO module defines the motor as stopped and
the SSE
completed indication goes on. The acknowledgement becomes allowed as soon as the
SSE request has been removed (step 4).
4
The SSE request is removed.
5
After the acknowledgement, the SSE, STO and SBC functions are deactivated and the
control is given back to the drive, which controls the brake from now on. The indications
goes off.