330 Verification and validation
Validation of the PROFIsafe connection
Follow the steps below to validate the PROFIsafe connection:
1. Make sure that the PROFIsafe communication is enabled in FSO parameter
.
2. Make sure that the fieldbus module (FENA-21 or FPNO-21) is configured into use
in the drive. See
ACS880 primary control program firmware manual
and
FENA-01/-11/-21 Ethernet adapter module user's manual
(3AUA0000093568
[English]) or
FPNO-21 PROFINET fieldbus adapter module user's manual
(3AXD50000158614 [English])
.
3. Make sure that correct option slot is configured for PROFIsafe. The value of FSO
module parameter
must correspond to the
FBA channel of the fieldbus interface (FBA A or FBA B).
4. Make sure that the fieldbus module is configured correctly in drive parameter
group 51 or 54 (depends on which FBA channel [FBA A or FBA B] is used). See
the appropriate fieldbus module manual for details. Most importantly:
•
parameter
51.02/54.02 Protocol/Profile
must be set to configure one of the
PROFINET profiles,
•
parameter
51.21
or
54.21
must be set to
Enabled
(0)
to enable sending of the
PROFIsafe diagnosis messages.
5. Make sure that the PROFIsafe watchdog time for the fieldbus module that is
configured in the controller station is calculated as specified in section
on page
6. Make sure that the PROFIsafe address (F_Dest_Add) of the FSO module is
unique in the network and the same value is set in FSO parameter
and in the safety controller station.
7. Make sure that the PROFIsafe address (F_Source_Add) of the safety PLC is
unique in the network.
8. Make sure that the PROFIsafe speed scaling value in FSO parameter
is calculated as specified in
section
the safety fieldbus communication
on page
9. Make sure that the safety controller station is commissioned according to its
instructions. Make sure that the correct GSD-file is in use, for example, a correct
PS profile is in use.
10. Make sure that the communication between controller and PROFINET/
PROFIsafe devices is established properly.
11. Verify by activating some suitable safety function in each of the FSOs modules in
PROFIsafe network, that the safety function is activated in correct drive.
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...