![ABB FSO-12 User Manual Download Page 157](http://html.mh-extra.com/html/abb/fso-12/fso-12_user-manual_2726157.webp)
PROFIsafe 157
Transitions between states
This table describes the transitions between the FSO module states. The numbering
of the transitions refer to the transitions shown in the state diagrams on page
ID
From
To
Description
1
Start-up
Safe (Module
passivation
with a
command)
The FSO module goes to this state directly after
Start-up during a normal start-up.
2
Operational
Start-up
The FSO module goes to this state by cycling
power of the FSO module or by giving the reset
command via the drive (parameter
96.09 FSO
reboot
, see the drive firmware manual).
3
Start-up
Safe (Module
passivation)
PROFIsafe watchdog time or PROFIsafe
communication error was detected directly after
Start-up.
4
Safe (Module
passivation)
Start-up
The FSO module goes to this state by cycling
power of the FSO module or by giving the reset
command via the drive (parameter
96.09 FSO
reboot
, see the drive firmware manual).
5
Start-up
Fail-safe
Fatal error(s) (CPU test, RAM test, etc. failed)
detected.
6
Fail-safe
Start-up
The FSO module goes to the Start-up mode by
cycling power of the FSO module or by giving the
reset command via the drive (parameter
96.09
FSO reboot
, see the drive firmware manual).
7
Operational
Safe (Module
passivation &
reintegration)
Execution of at least one safety function
encountered a problem. The system reaches the
Safe state. As soon as at least one of the errors
can be acknowledged, it can be done locally, via
PROFIsafe, or automatically depending on the
FSO configuration.
8
Safe (Module
passivation &
reintegration)
Operational
All the related errors have been solved and
acknowledged.
9
Operational
Fail-safe
Fatal error(s) (CPU test, RAM test, etc. failed)
detected.
10
Operational
Safe (Module
passivation)
PROFIsafe watchdog time or PROFIsafe
communication error was detected.
11
Operational
Safe (Module
passivation
with a
command)
Command “activate_FV_C = 1” was sent from the
safety PLC.
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...