222 Configuration
FSO configuring procedure
The FSO parameters are set with the Drive composer pro PC tool. The names of the
FSO parameters and parameter settings are shown in the manual as they appear on
the screen when using the tool. See
Drive composer PC tool user's manual
(3AUA0000094606 [English]) for instructions on using the tool.
You must always check all parameter values to make sure that they are suitable for
your application. The pre-set values in a delivered FSO module or factory default
values are not valid for any safety application as such.
Note:
Configuration is only possible when the drive is not modulating or the FSO is in
the Safe state.
Note
: After you initially start up the FSO and also after you later modify any
application parameters or the configuration, you must check the safety of the entire
system by doing a verification according to the system safety verification plan and by
doing a validation of the correct operation of the safety application. See chapter
Verification and validation
.
1. Plan the configuration (parameter values) according to the safety system,
installation, wiring, etc.
2. Set the parameter values in the Drive composer pro PC tool.
a. Power up the drive and make sure that the motor is not running.
b. Connect your PC to the drive, start the Drive composer pro PC tool and select
Safety settings
.
c. Open the parameters for setting:
•
First start-up: Upload the parameters from the FSO to the PC tool (button
Read settings from drive
). A password is required.
Make a backup copy of the pre-set safety file (button
Save to file
).
•
Existing configuration: Open the configuration file (button
Load from file
).
Note
: When you upload parameters from the FSO module to the PC tool, the FSO
goes into the Configuration mode and indicates a fault (
). You can exit the
Configuration mode by rebooting the FSO module (by switching the power off and
on, with the
Reboot FSO
button or with drive parameter
96.09 FSO reboot
) or by
downloading the parameters to the FSO (steps 2.e - f below).
d. Set the parameter values.
•
General parameters: Start from the general parameters. Check at least
that the motor parameters are correct.
•
Safety fieldbus communication (if used): Set up the communication
between the safety PLC and FSO module.
•
I/O: Check that the I/O parameters are set according to the installation
(wiring) plan. Set diagnostic pulsing for I/Os when necessary. Check
possible safety relays and cascade connections.
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...