Fault tracing 353
Faults, warnings and events
Code
(hex)
Name
Cause
What to do
Faults
7A81
TUCSO fault
FSO subsystem fault
Contact your local ABB
representative.
7A8B
FSO general fault
FSO module is in the
Configuration mode.
FSO module also
generates this fault after
certain malfunctions
which the FSO module
indicates by warnings.
First the FSO module
generates a warning
indication which allows
the drive to control the
system to a safe state.
After this the drive trips.
See the warning log for more
information on the actual cause.
3)
7A90
FSO stop
completed
FSO module has
completed the STO, SS1
or SSE function.
-
1)
7A91
FSO safe speed
limit
Motor actual speed
exceeded an SLS1...4 or
SMS limit of the FSO
module.
Make sure that SLS and SMS trip
limits are defined properly.
Check that transient mute time values
are defined properly (
).
2) 3)
7A92
FSO out of eme
ramp
Motor speed was not
inside the ramp window
during the SSE function.
Make sure that the drive can
decelerate the load using the ramp
time (
).
2)
7A93
FSO ramp
coasted
Drive coasted the motor
to stop instead of using
the ramp.
Check that the FSO module speed
limit for stopping the ramp
deceleration is not excessive
(
).
2)
7A94
FSO out of safe
ramp
Motor speed was not
inside the ramp window
during the SS1 function.
Make sure that the drive can
decelerate the load using the ramp
time (
).
2)
7A97
FSO premature
POUS
FSO received an external
POUS request while the
drive was still modulating.
It is recommended to activate the
POUS function only when the drive is
stopped.
7A98
FSO undefined
fault
FSO new version,
undefined fault in the dive
event system.
Contact your local ABB
representative.
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...