288 Parameters
200.112 SAR1 ramp time to
zero
Sets the target time for the SAR1 ramp
(used in the SS1 and SLS functions).
Target time = Time in which the drive
decelerates the motor from speed
to zero.
Note
: With value
0 ms
, the drive (parameter
23.23 Emergency stop time
) defines the safe
stop ramp. The FSO module monitors the
actual ramp using SAR1 parameters (ramp
monitoring) or parameter
(time monitoring).
1 ms
0…1,800,000 ms
Time.
200.201 Drive general
settings version
Shows the version of the drive general
safety settings (includes parameters
,
and
Version 1
Version 1.
200.202 SAR speed scaling
Sets a speed value that the FSO module
uses as a reference point in ramp time
calculations.
See section
on page
.
1500 rpm
0…35880 rpm
Speed
200.222 Safety bus type
Sets the type of the safety fieldbus (if used).
Note
: To activate the safety fieldbus, you
must also set parameter
to value
.
Not used
The safety fieldbus is not used.
PROFIsafe
PROFIsafe
200.223 Safety fieldbus
adapter slot
Sets the slot in which the safety fieldbus
adapter is installed.
Note
: The slots on the drive control board
are defined by drive parameters
50.01
(FBA
A) and
50.31
(FBA B). See the drive
firmware manual.
FBA A
The safety fieldbus adapter is in slot FBA A.
FBA B
The safety fieldbus adapter is in slot FBA B.
200.254 CRC of the
configuration
Shows the FSO configuration checksum.
0
0…65535
Checksum
Index
Name/Value
Description
Factory
default
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...