PROFIsafe 159
24
Safe (Module
passivation with a
command)
Safe (User
acknowledgem
ent request)
Command “activate_FV_C = 0” has been
received and “OA_Req_S = 1”.
25
Safe (Module
passivation with a
command)
Fail-safe
Fatal error(s) (CPU test, RAM test, etc. failed)
detected.
26
Safe (Module
passivation with a
command)
Start-up
The FSO module goes to this state by cycling
power of the FSO module or by giving the reset
command via the drive (parameter
96.09 FSO
reboot
, see the drive firmware manual).
27
Safe (Module
passivation with a
command)
Operational
No module error and “activate_FV_C = 0”.
28
Safe (Module
passivation &
reintegration)
Safe (Module
passivation)
PROFIsafe watchdog or PROFIsafe
communication error was detected.
29
Safe (Module
passivation &
reintegration)
Safe (Module
passivation
with a
command)
Command “activate_FV_C = 1” was sent from the
safety PLC.
30
Safe (User
acknowledgement
request)
Safe (Module
passivation &
reintegration)
OA_C (positive edge) was set by the PROFIsafe
F-Host, but there are existing errors in the active
safety functions or there are errors that need to be
acknowledged.
31
Safe (Module
passivation with a
command)
Safe (Module
passivation &
reintegration)
Command “activate_FV_C = 0” was set by the
PROFIsafe F-Host but there are existing errors in
the active safety functions or there are errors that
need to be acknowledged.
32
Any state when the
motor is not
running
Configuration
Drive composer pro connects to the FSO module
and as a result the FSO goes to the Configuration
sate.
33
Configuration
Start-up
From the Configuration mode, it is possible to go
only to the Start-up mode by cycling power of the
FSO module or by giving the reset command via
the drive (parameter
96.09 FSO reboot
, see the
drive firmware manual).
ID
From
To
Description
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...