270 Configuration
How to configure SMS, version 2
Example:
The figure below shows an example of the SMS, version 2 set-up:
• SMS function version 2 activated (
=
Version 2
)
• SMS limit positive (
=
1750
)
• SMS limit negative (
-1150
)
• SMS trip limit positive 1800.0 rpm (
SMS trip limit positive
= 1800 rpm
)
• SMS trip limit negative -1200.0 rpm (
SMS trip limit negative
=
-1200 rpm
)
• SSE function configured as immediate STO
Immediate STO
).
• See also section
.
Note
: If you also use an SLS function, the SMS positive and negative trip limits must
be more than the speed defined by the corresponding SLS positive trip limit and less
than the speed defined by the corresponding SLS negative trip limit, respectively.
Related safety functions
The FSO module activates the SSE function if the motor speed hits an SMS trip limit.
See section
.
= 1800 rpm
= 1750 rpm
= -1150 rpm
= -1200 rpm
Version 2
Speed
Time
SSE activated