256 Configuration
How to configure SSE with speed limit activated SBC, SBC before
STO
The configuration of the SSE with speed limit activated SBC, SBC before STO is
identical to the configuration of the same SS1 function with these differences:
• SSE input parameters (
and
) are used
instead of SS1 input parameters
• SSE output parameters (
are used instead of SS1 output parameters.
• type of the SSE function must be set: SSE with emergency ramp (
=
Emergency ramp
)
• SAR0 emergency ramp and monitoring limits are used instead of SAR1
• monitoring method is set with parameter (
Time
or
Ramp
)
• security delay for activating the drive STO is set with parameter
• delay for activating the brake after the speed limit has been reached is set with
parameter
SSE ramp zero speed delay for STO
.
Note
: If you configure the SSE with speed limit activated SBC function, this activates
the same function in the SS1 function (see section
How to configure SS1 with speed
limit activated SBC, SBC before STO
on page
). This does not activate the SBC
in the STO function. If necessary, configure the SBC also in the STO function (see
section
on page
). See also the note on page
.
For more information on the SSE with speed limit activated SBC, SBC before STO
SBC function, see page
Related safety functions
The SSE function uses SAR0 ramp parameters. See section
on
page
The FSO module activates the STO function if the motor speed hits a monitoring limit
(SSE with time or ramp monitoring). See section
on page
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...