Configuration 257
Configuring SAR
How to configure SARn
To configure the SARn (n = 0…1), set the FSO parameters listed below to appropriate
values using the Drive composer pro PC tool. See parameter groups
page
on page
. See also section
on page
Example:
The figure below shows an example of a SAR0 monitoring set-up:
• SAR0
• ramp time from Scaling speed to zero: 1000 ms
200.102 SAR0 ramp time to zero
= 1000 ms
)
• Scaling speed: 1500 rpm (
1500 rpm
)
• initial range for monitoring: 100 ms (
100 ms
)
• minimum allowed ramp time: 500 ms
500 ms
)
• maximum allowed ramp time: 1000 ms
=
1500 ms
).
Note:
If you use SAR1 in several safety functions at the same time, tune it according
to the function which requires the tightest monitoring range.
= 500 ms
= 1500 ms
1000 ms
= 1500 rpm
SAR0
Time
Speed
= 100 ms