Safety functions 93
SSE when drive modulation is lost during deceleration ramp
The behavior of SSE function in a situation where modulation is lost during
deceleration ramp is similar to SS1 function with ramp monitoring, see section
ramp functions when drive modulation is lost
Step Description
1
The SSE request is received (for example, from the I/O).
2
After time D has elapsed, the drive starts to ramp down the motor speed. SAR0
parameter
defines the deceleration ramp. The FSO starts the SAR0 ramp
monitoring (parameters
and
).
3
The motor speed goes below the SBC speed limit (A), the FSO stops the SAR0
monitoring and activates the SBC function.
The FSO starts counters for times B and C.
Note
: You can define an extra delay (parameter
, not shown in the figure)
before the FSO activates the SBC function. This affects also the STO activation (step
4).
3b
If the motor speed hits a ramp monitoring limit, the FSO activates the STO function.
See
section
on page
for more information on how to configure
the STO function.
4
After time B has elapsed, the FSO activates the drive STO function.
5
The SSE request is removed.
6
After time C has elapsed, the FSO defines the motor as stopped, the SSE completed
indication goes on and the acknowledgement becomes allowed as soon as the SSE
request has been removed (step 5).
7
After the acknowledgement, the SSE, STO and SBC functions are deactivated and the
control is given back to the drive, which is allowed to modulate again. The indications
go off.
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...